EasyManua.ls Logo

Siemens CU240S DP-F - Page 398

Siemens CU240S DP-F
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Faults and Alarms
List of Fault and Alarm messages
3-398
ยฉ Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Remedy: โ€ข r0949 = 100 or 200
Increase the ramping times p1120/p1121 or the safety tolerance p9691/p9891,
check the motor parameters (p0394 - p0311) or run the motor identification (p1910) again.
Decrease the rate of switching the safety signals or lower the cycle time of the PLC.
โ€ข r0949 = 101 or 201
Increase the ramping times p1120/p1121 or the safety tolerance p9691/p9891,
check the motor parameters (p0394 - p0311) or run the motor identification (p1910) again.
โ€ข r0949 = 102 or 202
Increase the ramping times (p1120, p1121) so that deviation between reference and actual frequency is mini-
mized.
Increase the safety tolerance p9691/p9891 or run the motor identification (p1910) again for better tuning of the
observer and controllers.
โ€ข r0949 = 104 or 204
Acknowledge the fault once more
Power cycle the CU
โ€ข r0949 = 106 or 206
Check connection with safe brake module and mechanical brake
Check the 24 V power supply for safe brake module
โ€ข r0949 = 107 or 207
Check connection between CU and power module
Power cycle the CU
โ€ข r0949 = , 108, or 208
Decrease the rate of switching the safe digital inputs or increase debounce delay time p9650/p9850.
โ€ข r0949 = 109 or 209
Power cycle the CU
Change CU

Table of Contents

Other manuals for Siemens CU240S DP-F

Related product manuals