Monitoring types
The converter monitors its temperature using the following monitoring types:
I
2
t monitoring (alarm A07805, fault F30005)
Measuring the chip temperature of the converter (alarm A05006, fault F30024)
Measuring the heat sink temperature of the converter (alarm A05000, fault F30004)
Function description
Overload response for p0290=0
The converter responds depending on the control mode that has been set:
In vector control, the converter reduces the output current.
In U/f control, the converter reduces the speed.
Once the overload condition has been removed, the converter re-enables the output current
or speed.
If the measure cannot prevent a converter thermal overload, then the converter switches o󹪜
the motor with fault F30024.
Overload response for p0290=1
The converter immediately switches o󹪜 the motor with fault F30024.
Overload response for p0290=2
We recommend this setting for drives with square-law torque characteristic, e.g. fans.
Advanced commissioning
7.23Converter protection using temperature monitoring
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 317

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G115D and is the answer not in the manual?

Siemens SINAMICS G115D Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G115D
CategoryDC Drives
LanguageEnglish

Related product manuals