6.5 Commissioning
After being switched on, the converter starts extensive self-configuration. The most important
data is read from the electronic rating plate of the motor connected using the OCC cable and
used for the self-configuration. The following steps are required to complete the
commissioning:
Name assignment of the converter (initialization) according to its technical application
One Button Tuning for the optimal controller setting of the converter
Note
Rights required for commissioning
Administrator rights are essential for commissioning via the Web server:
( "Users and access rights (Page 114)")
6.5.1 Assigning the drive name
During converter commissioning you can allocate a specific system name.
Procedure
1. Select "Commissioning" and "Device" in the navigation.
Figure 6-5 Device name
2. Enter a new drive name in the "Drive name" field.
Do not use special characters for the drive name. The name cannot be saved when special
characters are used.
3. Click "Apply Settings" to save the changes in the RAM of the device.
The assigned drive name is displayed in the status bar of the web browser, on the overview
page for the converter data and on the tab of the browser window.
4. Click to save the data permanently.
Commissioning and diagnostics in the Web server
6.5 Commissioning
SINAMICS S210 servo drive system
118 Operating Instructions, 12/2017, A5E41702836B AA