Siemens SINAMICS S210 - Topology: Serial Number Different

Siemens SINAMICS S210
768 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cause: The topology comparison has detected differences in the actual topology and target topologies in the electronic rating plate.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex: aa = component number (%1), bb = component class of the target topology (%2), cc = component class
of the actual topology (%3), dd = difference (%4)
dd = 01 hex = 1 dec:
Different component type.
dd = 02 hex = 2 dec:
Different article number.
dd = 03 hex = 3 dec:
Different manufacturer.
dd = 04 hex = 4 dec:
For a multi-component slave, the incorrect subcomponent (index) is connected (e.g. Double Motor Module X201 instead
of X200) - or only a part of a multi-component slave is set to "deactivate and not available".
dd = 05 hex = 5 dec:
NX10 or NX15 used instead of CX32.
dd = 06 hex = 6 dec:
NX10 or NX15 used instead of CX32.
dd = 07 hex = 7 dec:
Different number of connections.
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: Adapting topologies:
- connect the expected component (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Topology comparison - if required, adapt the comparison level:
- parameterize the topology comparison of all components (p9906).
- parameterize the topology comparison of one components (p9907, p9908).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
A01425 Topology: Serial number different
Message value: Component: %1, %2, differences: %3
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected differences in the actual and target topologies in relation to one component. The
serial number is different.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = reserved
cc = number of differences (%3)
bb = component class (% 2)
aa = component number (%1)
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA 335