Acknowledge: POWER ON
Cause: EEPROM data error of the HF Damping Module.
Fault value (r0949, interpret hexadecimal):
0: The EEPROM data read in from the HF Damping Module is inconsistent.
1: EEPROM data is not compatible to the firmware of the HF Damping Module.
Additional values:
Only for internal Siemens troubleshooting.
Remedy: For fault value = 0:
Replace the HF Damping Module or update the EEPROM data.
For fault value = 1:
If necessary, upgrade the firmware to a later version.
Note:
HF Damping Module
A37056 (F) HF Damping Module: Heat sink overtemperature
Message value: %1
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The temperature of the HF Damping Module heat sink has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Alarm value (r2124, interpret decimal):
Temperature [0.01 °C].
Remedy: - check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
Note:
HF Damping Module
Reaction upon F: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
A37310 (F) HF Choke Module: Overtemperature
Message value: %1
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The temperature of the HF Choke Module heat sink has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Alarm value (r2124, interpret decimal):
Temperature [0.01 °C].
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
714 Operating Instructions, 12/2017, A5E41702836B AA