132: Free BICO interconnection inhibited via p0922.
133: Access method not defined.
200: Below the valid values.
201: Above the valid values.
202: Cannot be accessed from the Basic Operator Panel (BOP).
203: Cannot be read from the Basic Operator Panel (BOP).
204: Write access not permitted.
Remedy: - correct the parameterization in the commissioning tool and download the project again.
- enter the correct value in the specified parameter.
- identify the parameter that restricts the limits of the specified parameter.
A01097 (N) NTP server cannot be accessed
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The selected NTP server (p3105[0...3]) cannot be accessed. Time synchronization cannot be performed.
Note:
NTP: Network Time Protocol
Remedy: Correctly set the IP address of the NTP server, and check the connection to the NTP server.
Reaction upon N: NONE
Acknowl. upon N: NONE
A01099 (N) UTC synchronization tolerance violated
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The tolerance (p3109) set for UTC synchronization was violated.
Note:
UTC: Universal Time Coordinates
Remedy: Select the synchronization intervals shorter so that the deviation between the time of day master and drive system lies
within the tolerance.
Note:
The deviation when synchronizing is shown in r3107.
Reaction upon N: NONE
Acknowl. upon N: NONE
F01105 (A) CU: Insufficient memory
Message value: %1
Drive object: All objects
Reaction: OFF1
Acknowledge: POWER ON
Cause: Too many functions have been configured on this Control Unit (e.g. too many drives, function modules, data sets,
Technology Extensions, blocks, etc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - change the configuration on this Control Unit (e.g. fewer drives, function modules, data sets, Technology Extensions,
blocks, etc).
- use an additional Control Unit.
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA 311