Remedy: - re-commission the safety functions.
- upgrade the drive software.
- replace the memory card or drive.
For fault value = 129:
- activate the Safety Integrated commissioning mode.
- adapt the PROFIsafe address.
- copy the safety parameters and confirm the data change.
- exit the Safety Integrated commissioning mode.
- save all parameters or "Copy RAM to ROM".
- carry out a POWER ON (switch-off/switch-on).
Note:
SI: Safety Integrated
F30657 SI P2: PROFIsafe telegram number invalid
Message value: -
Drive object: All objects
Reaction: OFF2
Acknowledge: POWER ON
Cause: The PROFIsafe telegram number that has been set is not valid.
When PROFIsafe is enabled (p9601.3 = 1), then a telegram number greater than zero must be used.
The copy function was not used.
Note:
This fault does not result in a safety stop response.
See also: p9611, p60022, r60022
Remedy: Enter a valid PROFIsafe telegram number (p9611), then using the commissioning tool, copy the safety parameters and
confirm the data change.
F30659 SI P2: Write request for parameter rejected
Message value: %1
Drive object: All objects
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The write request for one or several Safety Integrated parameters in monitoring channel 2 was rejected.
Note:
See also fault F01659.
Remedy: Upgrade the firmware to later version.
F30664 Error while booting
Message value: %1
Drive object: All objects
Reaction: OFF2
Acknowledge: POWER ON
Cause: An error has occurred during booting.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA 525