Dependency: See also: r0082
r0034 Motor utilization thermal
Data type: FloatingPoint32 P group: Displays, signals Scaling: PERCENT
Description: Displays the thermal motor utilization taking into account the ambient temperature set in p0613.
Dependency: See also: p0613
See also: F07011, A07012
NOTICE
After the drive is switched on, the system starts to determine the motor temperature with an assumed model value.
This means that the value for the motor utilization is only valid after a stabilization time.
r0037[0...20] Drive temperatures
Data type: FloatingPoint32 P group: Displays, signals Scaling: p2006
Description: Displays the temperatures of the drive components.
Index: [0] = Inverter maximum value
[1] = Depletion layer maximum value
[2] = Reserved
[3] = Reserved
[4] = Interior of power unit
[5] = Inverter 1
[6...12] = Reserved
[13] = Depletion layer 1
[14...20] = Reserved
Note
The value of -200 indicates that there is no measuring signal.
For index [0]:
Maximum value of the inverter temperatures (r0037[5...10]).
For index [1]:
Maximum value of the depletion layer temperatures (r0037[13...18]).
The maximum value is the temperature of the hottest inverter or depletion layer.
In the case of a fault, the particular shutdown threshold depends on the power unit, and cannot be read out.
r0039[0...2] Energy display
Data type: FloatingPoint32 P group: Displays, signals
Description: Display for the energy values at the drive output terminals.
Index: [0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
Note
For index [0]:
Difference between the energy drawn and energy that is fed back.
r0046 Enable signals status
Data type: Unsigned32 P group: Displays, signals
Description: Displays the status of the enable signals.
All enable signals are required to operate the drive. The enable signals are set by the control.
Bit field: Bit Signal name 1 signal 0 signal FP
00 OFF1 enable missing Yes No 7954
01 OFF2 enable missing Yes No -
02 OFF3 enable missing Yes No -
Parameters
12.2 List of parameters
SINAMICS S210 servo drive system
230 Operating Instructions, 12/2017, A5E41702836B AA