Requirements relating to shielded cables
Use cables with finely-stranded, braided shields.
Connect the shield at both ends of the cable.
Figure 3-2 Shield support with the shield terminal from the scope of supply of the MOTION-
CONNECT OCC cable.
Connect the shield to the shield support.
Do not interrupt the shield.
3.1.3 Electromechanical components
Surge voltage protection circuit
Connect surge voltage protection circuits to the following components:
Coils of contactors
Relays
Solenoid valves
Connect the surge voltage protection circuit directly at the coil.
Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors
for DC-operated coils.
Configuring
3.1 EMC-compliant installation of a machine or system
SINAMICS S210 servo drive system
38 Operating Instructions, 12/2017, A5E41702836B AA