5.3 Installing the converter
5.3.1 Installation conditions
When installing the converter carefully observe the conditions listed below in order to
guarantee reliable, continuous and trouble-free operation.
The converter is designed for installation in a control cabinet.
The converter is certified for use in environments with degree of pollution 2 without
condensation; i.e. in environments where no conductive pollution/dirt occurs. Condensation
is not permissible.
The converter fulfills degree of protection IP20.
EMC-compliant installation:
EMC-compliant installation of a machine or system (Page 35).
Additional requirements for plants and systems in the United States / Canada (UL/cUL)
A label with the following number is provided with the device: A5E36790112.
Note the instructions on the label and attach the label in a clearly visible location close to the
converter in the control cabinet.
Installation notes
Install the converter vertically with the flap for the LED display facing upwards.
Figure 5-2 Mounting position of the converter
Maintain the minimum clearances to other components.
Use the recommended hardware (screws M5) and comply with the specified torques.
Installing
5.3 Installing the converter
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA 87