Cause: The brake test was canceled as a result of incorrect control.
Alarm value (r2124, evaluate binary):
Alarm value 0:
The brake test was canceled as a result of a fault (brake opening time or brake closing time exceeded).
Bit 0:
The safe brake test was canceled by resetting the brake test selection.
Bit 1:
The safe brake test was canceled by resetting the brake test start.
Bit 2:
The brake is not configured in configured p10202.
There is a brake test configuration error. In this case, alarm A01785 is also output.
Note:
SBT: Safe Brake Test
See also: p10202
Remedy: - check parameterization of the brake test (p10202).
- check as to whether alarm A01785 is present, and if so, evaluate.
- carry out a safe acknowledgment.
- if required, restart the brake test.
A01783 SBT brake closing time exceeded
Message value: Fault cause: %1 bin
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The maximum time (11 s) to close the brake during the brake test was exceeded.
Alarm value (r2124, interpret binary):
Bit 0 = 1:
The brake was not able to be closed.
Note:
SBT: Safe Brake Test
Remedy: - when using an internal brake with external feedback signal, check whether the feedback signal is correctly interconnected
with the extended brake control.
- carry out a safe acknowledgment.
- restart the brake test.
A01784 SBT brake test canceled with fault
Message value: Fault cause: %1
Drive object: All objects
Reaction: NONE
Acknowledge: NONE