Siemens SINAMICS S210 - SI Motion P1 (CU): Axis Not Safely Referenced; SI Motion P1 (CU): Test Stop for Motion Monitoring Functions Running; SI Motion P1 (CU): Acceptance Test Mode Active

Siemens SINAMICS S210
768 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Remedy: If, after a longer period of time, the message is not automatically withdrawn, the following checks have to be made:
- check any other PROFIsafe communication messages/signals present and evaluate them.
- check the operating state of the F-Host.
- check the communication connection to the F Host.
Note:
STO: Safe Torque Off
See also: p9601
Reaction upon F: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
Reaction upon N: NONE
Acknowl. upon N: NONE
C01797 SI Motion P1 (CU): Axis not safely referenced
Message value: %1
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The standstill position saved before switching off does not match the actual position determined at switch-on.
Message value (r9749, interpret decimal):
1: Axis not safely referenced.
2: User agreement missing.
Remedy: If safe automatic referencing is not possible the user must issue a user agreement for the new position using the softkey.
This mean that this position is then designated as safety-relevant.
Note:
SI: Safety Integrated
C01798 SI Motion P1 (CU): Test stop for motion monitoring functions running
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The forced checking procedure (test stop) for the safe motion monitoring functions is currently in progress.
Remedy: Not necessary.
The message is automatically withdrawn when the test stop has been completed.
Note:
SI: Safety Integrated
C01799 SI Motion P1 (CU): Acceptance test mode active
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The acceptance test mode is active.
This means the following:
- the setpoint velocity limiting is deactivated (r9733).
Remedy: Not necessary.
The message is withdrawn when exiting the acceptance test mode.
Note:
SI: Safety Integrated
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
394 Operating Instructions, 12/2017, A5E41702836B AA