1. If you want to change the discrepancy time, click the "SI F-DI discrepancy time" field.
An input dialog with the same name opens. Adjust the set discrepancy time and confirm
with "OK".
2. If you want to change the debounce time, click the "SI STO/SS1 debounce time" field.
An input dialog with the same name opens. Set the debounce time and confirm with "OK".
3. Click "Continue".
The "Test stop" commissioning step is activated.
Variant C: Control via PROFIsafe and onboard terminals
The settings of variants A and B are combined in variant C.
As a consequence, the STO and SS1 functions can be independently controlled via PROFIsafe
and F-DI.