Reaction: NONE
Acknowledge: NONE
Cause: The trace parameter settings cannot be changed when the trace is active.
Remedy: - stop the trace before parameterization.
- if required, start the trace.
A02075 Trace: Pretrigger time too long
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The selected pretrigger time must be shorter than the trace time.
Remedy: Check the pretrigger time setting and change if necessary.
F02080 Trace: Parameterization deleted due to unit changeover
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The trace parameterization in the drive unit was deleted due to a unit changeover or a change in the reference parameters.
Remedy: Restart trace.
A02085 Message function: Parameterization error
Message value: Parameter: %1
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: A parameterization error was identified when starting the variable message function.
Alarm value (r2124, interpret decimal):
Incorrectly set parameter.
Remedy: Correct the parameter and restart.
Note:
The alarm is automatically withdrawn when stopping, or when successfully starting the variable message function
(p3290.0).
A02095 MTrace 0: multiple trace cannot be activated
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The following functions or settings are not permissible in conjunction with a multiple trace (trace recorder 0):
- measuring function
- long-time trace
- trigger condition "immediate recording start" (IMMEDIATE)
- trigger condition "start with function generator" (FG_START)
Remedy: - if required, deactivate the multiple trace (p4840[0] = 0).
- deactivate function or setting that is not permissible
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
412 Operating Instructions, 12/2017, A5E41702836B AA