Note
For two connections (Shared Device or system redundancy) the display in the index depends on the sequence in
which the connections are established.
The IP addresses of controllers 1 and 2 are displayed in r8961 and r8962.
The following states are displayed for system redundancy:
Primary controller: r8936[x] = 13
Backup controller: r8936[x] = 11
If value = 10:
If the connection remains in this state, then when using PROFINET IRT the following can apply:
- topology error (incorrect port assignment).
- synchronization missing.
r8937[0...5] PN diagnostics
Data type: Unsigned32 P group: -
Description: Display to diagnose the cyclic PROFINET connections.
Index: [0] = Number of cyclic connections
[1] = Number of send subslots of all connections
[2] = Number of send net data (bytes) of all connections
[3] = Number of receive subslots of all connections
[4] = Number of receive net data (bytes) of all connections
[5] = Connection type (RT, IRT)
Note
For index [5]:
Bit 0 = 1: there is at least one RT connection.
Bit 1 = 1: there is an IRT connection.
p8984[0...1] BI: Web server interface enable
Changeable: T Data type: Unsigned32 / Binary P group: -
Min: - Max: - Def: [0] 1 [1] 0
Description: Setting to enable the interface for access via the web server.
Index: [0] = Reserved
[1] = PROFINET X150
Dependency: See also: p8986
Note
BI:p8984[1] = 1 signal:
PROFINET interface X150 is enabled for access to the web server.
BI:p8984[1] = 0 signal:
PROFINET interface X150 is enabled for access to the web server.
p8986 Web server configuration
Changeable: T Data type: Unsigned16 P group: -
Min: - Max: - Def: 1101 bin
Description: Setting to activate and configure the "Web server" function in the drive.
It is possible to access the web server via the integrated Ethernet and PROFINET interfaces of the drive. The
addressing is realized via the set IP address.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Activating Yes No -
01 Only permit access via https Yes No -
02 Enable "SINAMICS" user Yes No -
03 Enable "Administrator" user Yes No -
Parameters
12.2 List of parameters
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA 261