r2136[0...63] Fault removed in days
Data type: Unsigned16 P group: Messages
Description: Displays the time in days referred to the day when the fault was rectified.
Dependency: See also: r0945, r0947, r0948, r0949, r2109, r2130, r2133
NOTICE
The time comprises r2136 (days) and r2109 (milliseconds).
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2145[0...63] Alarm received in days
Data type: Unsigned16 P group: Messages
Description: Displays the time in days referred to the day that the alarm occurred.
Dependency: See also: r2122, r2123, r2124, r2125, r2134, r2146
NOTICE
The time comprises r2145 (days) and r2123 (milliseconds).
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2146[0...63] Alarm removed in days
Data type: Unsigned16 P group: Messages
Description: Displays the time in days referred to the day when the alarm was cleared.
Dependency: See also: r2122, r2123, r2124, r2125, r2134, r2145
NOTICE
The time comprises r2146 (days) and r2125 (milliseconds).
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
p2175[0] Motor blocked speed threshold
Changeable: T, U Data type: FloatingPoint32 P group: Messages
Min: 0.00 [rpm] Max: 210000.00 [rpm] Def: 120.00 [rpm]
Description: Sets the speed threshold for the message "Motor locked".
Monitoring is deactivated with p2175 = 0.
Dependency: See also: F07900
Note
If the motor speed is less than the threshold value set in p2175 - and the motor is operated for longer than 200 ms at
the torque limit - then the motor is shut down and a fault is output.
p3103 UTC synchronization process
Changeable: T, U Data type: Integer16 P group: -
Min: 4 Max: 99 Def: 4
Description: Setting the synchronization process.
Value: 4: Network Time Protocol
99: No synchronization
Note
If value = 4:
Synchronization of the time in the drive with the time specified by the higher-level control system.
Parameters
12.2 List of parameters
SINAMICS S210 servo drive system
254 Operating Instructions, 12/2017, A5E41702836B AA