EasyManua.ls Logo

Siemens SINAMICS S210 - SI Motion: Axis Re-Configured; SI Motion: Data Save Problem for the NVRAM

Siemens SINAMICS S210
768 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cause: - it is not permissible to enable actual value synchronization for a 1-encoder system.
- it is not permissible to simultaneously enable actual value synchronization and a monitoring function with absolute
reference (SCA/SLP).
- it is not permissible to simultaneously enable actual value synchronization and safe position via PROFIsafe.
Note:
This fault results in a STOP A that cannot be acknowledged.
Remedy: - Either select the "actual value synchronization" function or parameterize a 2-encoder system.
- either deselect the function "actual value synchronization" or the monitoring functions with absolute reference (SCA/SLP)
and carry out a POWER ON.
- either deselect the "actual value synchronization" function or do not enable "Safe position via PROFIsafe".
Note:
SCA: Safe Cam / SN: Safe software cam
SI: Safety Integrated
SLP: Safely Limited Position / SE: Safe software limit switches
SP: Safe Position
See also: p9501
C01689 SI Motion: Axis re-configured
Message value: Parameter: %1
Drive object: All objects
Reaction: OFF2
Acknowledge: POWER ON
Cause: The axis configuration was changed (e.g. changeover between linear axis and rotary axis).
Parameter p0108.13 is internally set to the correct value.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
Parameter number of parameter that initiated the change.
Remedy: The following should be carried out after the changeover:
- exit the safety commissioning mode (p0010).
- save all parameters
- carry out a POWER ON.
Once the drive has been switched on, safety message F01680 or F30680 indicates that the checksums have changed in
the drive. The following must, therefore, be carried out:
- activate safety commissioning mode again.
- complete safety commissioning of the drive.
- exit the safety commissioning mode (p0010).
- save all parameters
- carry out a POWER ON.
Note:
For the commissioning tool, the units are only consistently displayed after a project upload.
F01690 SI Motion: Data save problem for the NVRAM
Message value: %1
Drive object: All objects
Reaction: NONE (OFF1, OFF2, OFF3)
Acknowledge: POWER ON
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
372 Operating Instructions, 12/2017, A5E41702836B AA

Table of Contents

Related product manuals