r60022 PROFIsafe telegram selection
Data type: Unsigned16 P group: Safety Integrated
Description: Displays the number of the PROFIsafe send and receive telegrams.
The drive takes this number from the higher-level control system.
Value: 0: No PROFIsafe telegram selected
30: PROFIsafe standard telegram 30, PZD-1/1
901: PROFIsafe SIEMENS telegram 901, PZD-3/5
Dependency: See also: p9611
r60122 PROFIdrive SIC/SCC telegram selection
Data type: Unsigned16 P group: Communications
Description: Displays the telegram for the safety information channel (SIC) / safety control channel (SCC).
SIC/SCC telegram p60122 is attached directly to the PZD telegram p0922.
Value: 700: Supplementary telegram 700, PZD-0/3
701: Supplementary telegram 701, PZD-2/5
999: No telegram
Dependency: For p8864 equal to 999, then p60122 is locked.
r61000[0...239] PROFINET Name of Station
Data type: Unsigned8 P group: -
Description: Displays PROFINET Name of Station.
r61001[0...3] PROFINET IP of Station
Data type: Unsigned8 P group: -
Description: Displays PROFINET IP of Station.