6. Click "OK".
The tuning through the One Button Tuning starts. No entries are possible during the tuning.
After the tuning has been completed, a message appears as to whether the "One Button
Tuning" was successful - or not. If the OBT was not successful, then optimization must be
repeated, possibly with modified entries.
Figure 6-8 View after performing the One Button Tuning
A list in the lower part of the window shows how the settings have been changed by the
One button tuning.
Note
If the machine vibrates or whistles at certain speeds following One Button Tuning, then the
dynamic response setting is too high. In this case, select a lower dynamic response and
repeat the One Button Tuning.
7. After completing the controller tuning, you must return the master control over the converter.
Click "Return control".
8. Confirm the confirmation prompt with "Confirm".
The color bar is no longer displayed.
9. Click to save the data permanently.
Result
When One Button Tuning is completed, the basic commissioning of the converter is finished.
All other parameters are automatically preset according to the motor characteristic.