Figure 3-1 Routing converter cables inside and outside a control cabinet
Routing cables outside the control cabinet
● Maintain a minimum clearance of 25 cm between cables with a high level of interference
and cables with a low level of interference.
● Use shielded cables for the following connections:
– Converter motor cable
– Cable between the converter and braking resistor
– Signal and data cables
Configuring
3.1 EMC-compliant installation of a machine or system
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA 37