Connection examples and cable cross-sections
① Line filter (optional) ② Group terminals
Sum of the input currents of all converters ≤ 24 A
● Fuses:
3NA3812 or class J 30 A for UL/CSA
● Cables for the line connection up to the terminal box
4 mm
2
, dimensioned for
I
rms
≥ 32 A
rms
at 50 °C
● Cables for the connection from the terminal box to the converter
2.5 mm
2
, dimensioned for
I
rms
≥ 18.5 A at 50 °C
Figure 3-5 Connection example for 230 V 1 AC
Configuring
3.2 Permissible line supplies and connection options
SINAMICS S210 servo drive system
42 Operating Instructions, 12/2017, A5E41702836B AA