Remedy: - check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
Note:
HF Choke Module (reactor module)
Reaction upon F: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
F37311 HF Choke Module: Heat sink overtemperature
Message value: %1
Drive object: All objects
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: The temperature of the HF Choke Module heat sink has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Fault value (r0949, interpret decimal):
Temperature [0.01 °C].
Remedy: - check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
Notice:
This fault can only be acknowledged after this alarm threshold for alarm A05000 has been undershot.
Note:
HF Choke Module (reactor module)
A37312 (F) HF Choke Module: Overtemperature or fan failure
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The HF Choke Module signals an overtemperature or fan failure.
Fault F37313 is output if the alarm is present for longer than 30 s.
Remedy: - the cable between the HF Choke Module and the HF Damping Module has been withdrawn or is defective (X21).
- check the fan of the HF Choke Module and replace if necessary.
- check whether the ambient temperature is in the permissible range.
Note:
HF Choke Module (reactor module)
HF Damping Module
Reaction upon F: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY (POWER ON)
F37313 HF Choke Module: Overtemperature or fan failure
Message value: -
Drive object: All objects
Reaction: OFF2