Remedy: In general:
- check the line supply voltage at the input terminals.
- check the line supply voltage setting (p0210).
For booksize drive units, the following applies:
- wait (approx. 8 minutes) until the precharging resistors have cooled down. For this purpose, preferably disconnect the
infeed unit from the line supply.
For 5):
- carefully observe the permissible precharging frequency (refer to the appropriate Equipment Manual).
For 6):
- check the total capacitance of the DC link and reduce in accordance with the maximum permissible DC link capacitance
if necessary (refer to the appropriate Equipment Manual)
For 7):
- interconnect the ready-for-operation signal from the infeed unit (r0863.0) in the enable logic of the drives connected to
this DC link
For 8):
- check the connections of the external line contactor. The line contactor must be open during DC link fast discharge.
For 9):
- check the DC link for ground faults or short circuits.
For 11):
- check the DC link voltage of the infeed (r0070) and Motor Modules (r0070).
If the DC link voltage generated by the infeed (or external) is not displayed for the Motor Modules (r0070), then a fuse has
ruptured in the Motor Module.
See also: p0210
A30030 Power unit: Internal overtemperature alarm
Message value: %1
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The temperature inside the drive converter has exceeded the permissible temperature limit.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - possibly use an additional fan.
- check whether the ambient temperature is in the permissible range.
Notice:
This alarm is automatically withdrawn once the permissible temperature limit value has been fallen below minus 5 K.
A30031 Power unit: Hardware current limiting in phase U
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA 503