EasyManua.ls Logo

Siemens SINAMICS S210 - Drive: Motor Temperature Model Configuration Fault; Drive: Motor Temperature Model Configuration Alarm

Siemens SINAMICS S210
768 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Remedy: - check the motor load and if required, reduce.
- check the motor ambient temperature.
- check activation of the motor temperature model (p0612).
Motor temperature model 1 (I2t):
- check the thermal time constant (p0611).
- check alarm threshold.
Motor temperature model 3:
- check the motor type.
- check alarm threshold.
- check the model parameters.
See also: r0034
Reaction upon N: NONE
Acknowl. upon N: NONE
F07013 Drive: Motor temperature model configuration fault
Message value: %1
Drive object: All objects
Reaction: OFF2 (NONE, OFF1, OFF3, STOP2)
Acknowledge: IMMEDIATELY
Cause: A fault has occurred in the configuration of the motor temperature model.
Fault value (r0949, interpret decimal):
300:
Motor temperature model 3: The sensor does not supply the necessary sensor temperature for the thermal model.
301:
Motor temperature model 3: The sensor type is unknown.
302:
Motor temperature model 3: At least one other temperature model was simultaneously activated.
303:
Motor temperature model unknown in the actual firmware version.
Remedy: - check the encoder type.
- check the motor type.
- check activation of the motor temperature model (p0612).
- check the parameters of the motor temperature model (p5350 and following).
A07014 (N) Drive: Motor temperature model configuration alarm
Message value: %1
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: A fault has occurred in the configuration of the motor temperature model.
Alarm value (r2124, interpret decimal):
1:
All motor temperature models: It is not possible to save the model temperature
300:
Motor temperature model 3: Threshold value for alarm (r5398) is higher than the threshold value for fault (r5399).
Remedy: - set the response for motor overtemperature to "Alarm and fault, no reduction of I_max" (p0610 = 2).
- check and correct the threshold values (r5398, r5399).
Reaction upon N: NONE
Acknowl. upon N: NONE
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
426 Operating Instructions, 12/2017, A5E41702836B AA

Table of Contents