Setup
3.4 Inputs and outputs
FST030
146 Function Manual, 04/2017, A5E35693328-AA
Setting
256 Standard density above alarm limit; 257 Standard density above warning limit; 258
Standard density below warning limit; 259 Standard density below alarm limit; 260 API
gravity above alarm limit; 261 API gravity above warning limit; 262 API gravity below warn-
ing limit; 263 API gravity belwo alarm limit; 264 Standard API gravity above alarm lim..; 265
Standard API gravity above warning li..; 266 Standard API gravity below warning li..; 267
Standard API gravity below alarm limit; 268 Specific gravity above alarm limit; 269 Specific
gravity warning limit; 270 Specific gravity below warning limit; 271 Specific gravity below
alarm limit; 272 Std. spec. grav.above alarm limit; 273 Std. spec. grav. above warning limit;
274 Std. spec. grav. bel. warning limit; 275 Std. spec. grav. bel. alarm limit;276 LiquIdent
above alarm limit; 277 LiquIdent above warning limit; 278 LiquIdent below warning limit;
279 LiquIdent below alarm limit
Path
Setup → Inputs and outputs → Channel 3 - input/output → Status output → Process alarms
3.4.5.8.8 Totalizer alarms
Description
Selection of alarm items that impact the output. Applicable if Status mode = Alarm item.
For hydrocarbon and gas applications only.
Setting
136 Totalizer 1 above alarm limit; 137 Totalizer 1 above warning limit; 138 Totalizer 1 -
below warning limit; 139 Totalizer 1 below alarm limit; 140 Totalizer 2 above alarm limit;
141 Totalizer 2 above warning limit; 142 Totalizer 2 below warning limit; 143 Totalizer 2
below alarm limit; 144 Totalizer 3 above alarm limit; 145 Totalizer 3 above warning limit;
146 Totalizer 3 below warning limit; 147 Totalizer 3 below alarm limit
Setup → Inputs and outputs → Channel 3 - input/output → Status output → Totalizer alarms
3.4.5.8.9 Device alarms
Description
Device alarms - If one of the selected events appears this affects the status icon, the related
status output, and the alarm on the communication interface.
Setting
148 Transm. temp. above alarm limit; 149 Transm. temp. below alarm limit; 150 Sensor
signal disrupted; 159 Internal error in transmitter
Default None
Setup → Inputs and outputs → Channel 3 - input/output → Status output → Device alarms