Setup
3.4 Inputs and outputs
FST030
168 Function Manual, 04/2017, A5E35693328-AA
Setting
Volume flow; Mass flow; Standard volume flow (only hydrocarbon and gas applications);
Flow velocity; Sound velocity; LiquIdent (only hydrocarbon applications); Density; Kinemat-
ic viscosity; Pressure; Medium temperature; Standard density (only hydrocarbon and gas
applications); Standard kinematic viscosity (only hydrocarbon applications); API gravity
(only hydrocarbon applications); Standard API gravity (only hydrocarbon applications);
Specific gravity (only hydrocarbon applications); Standard specific gravity (only hydrocar-
bon and gas applications); Auxiliary temperature; Sen
sor temperature; Standardizing factor
(only hydrocarbon and gas applications)
Setup → Inputs and outputs → Channel 4 - input/output → Current output → Process value
3.4.7.5.2 Direction
Description
Flow direction filter applicable for process values mass flow/volume flow/flow
velocity/standard volume flow rate (only hydrocarbon and gas applications).
Positive; Negative; Bidirectional; Bidirectional (symmetric)
Setup → Inputs and outputs → Channel 4 - input/output → Current output → Direction
3.4.7.5.3 Loop current scale
Description
Sets current output scaling according to desired measurement range. Format: <Nominal
range> (<lower fault current>) <lower saturation limit> to <upper saturation limit> (<upper
fault current>) [<Description>]
Setting 4 to 20 mA (3.50) 3.8 to 20.5 (22.6) NAMUR
4 to 20 mA (3.75) 4.0 to 20.8 (22.6) US
4 to 20 mA (0.00) 4.0 to 20.5 (22.0)
4 to 20 mA (2.00) 4.0 to 24.0 (25.0)
0 to 20 mA (0.00) 0.0 to 20.5 (22.0)
0 to 20 mA (0.00) 0.0 to 24.0 (25.0)
4 to 20 mA (3.50) 3.8 to 20.5 (22.6) NAMUR
Path
Setup → Inputs and outputs → Channel 4 - input/output → Current output → Loop current