204
Solution Ultima 844/862/880 Installation Manual
0 Day Alarm Latching
This output will operate w
hen a zone programmed for day alarm has been triggered. The
output will reset when the button has been pressed. Day alarm may be turned on and
off by holding down the
4 button. Refer to Day Alarm Zones on page 164 for
programming zones to operate for day alarm.
If the control panel has been partitioned, pressing the
button on a CP5 Area
Addressble codepad other than the zone was allocated, or pressing the button on a
CP5 Master Partitioned Codepad will not reset the output. You can only reset this output
on the area codepad that the zone has been allocated to.
10 Day Alarm Enabled
This output will operate as soon as day alarm has been enabled. The output will reset when
day alarm has been turned off.
Day alarm can be turned on and off by holding down the
4 button. Three beeps indicates
that day alarm has been turned on, two beeps indicates that day alarm has been turned off.
Refer to Day Alarm Zones on page 164 for programming zones to operate for day alarm.
11 Telephone Line Fail
This output will operate when the in-built telephone line fault module detects that the
telephone line has been disconnected for a period of approximately 40 seconds. The output
will reset once the telephone line has been restored continuously for more than 40 seconds.
This output will not operate unless Option 1 in “LOCATION 176” on page 149 has been
enabled.
12 Kiss-Off Received
This output will operate after the control panel has successfully sent to the receiving party.
13 Fuse Fail
This output will operate when either the 1 Amp codepad fuse or the 1 Amp accessories fuse
fails. The output will reset once the faulty fuse has been replaced.
14 AC Fail
This output will operate as soon as the AC mains has failed. The output will reset as soon
as the AC mains has restored. This output will operate regardless of Option 2 in
"LOCATION 438" on page 229 being set.
15 Low Battery
This output will operate when a dynamic battery test detects that the battery has failed or
the battery voltage has fallen below 10.5 volts. The dynamic battery test is performed
every four hours from when the system has been powered up or every time the system has
been armed in AWAY Mode, STAY Mode 1 or STAY Mode 2.
This output will reset only after a dynamic battery test reports the backup battery has
restored.
16 Horn Speaker Monitor Fail
If Option 2 – Enable Monitoring Of Horn Speaker in "LOCATION 436" on page 227 has
been selected, this output will operate when the horn speaker has been disconnected. The
output will reset when the horn speaker has been reconnected.
ISSUE162.DOC Electronics Design and Manufacturing Pty Limited