Description of device parameters Proline Promag 300 Modbus RS485
100 Endress+Hauser
Signal mode
Navigation  Expert → Input → Current input 1 to n → Signal mode (1610–1 to n)
Prerequisite The measuring device is not approved for use in the hazardous area with type of
protection Ex-i.
Description Use this function to select the signal mode for the current input.
Selection Passive
Active
Factory setting Active
Current span
Navigation  Expert → Input → Current input 1 to n → Current span (1605–1 to n)
Description Use this function to select the current range for the process value output and the upper
and lower level for signal on alarm.
Selection 4...20 mA
4...20 mA NAMUR
4...20 mA US
0...20 mA
Factory setting Country-specific:
4...20 mA NAMUR
4...20 mA US
Additional information Examples
Sample values for the current range: Current span parameter (→  106)
0/4 mA value
Navigation  Expert → Input → Current input 1 to n → 0/4 mA value (1606–1 to n)
Description Use this function to enter a value for the 4 mA current.
User entry Signed floating-point number
Factory setting 0