Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 133
Additional information Description
If no diagnostic event is pending, the switch output is closed and conductive.
Selection
• Alarm
The switch output signals only diagnostic events in the alarm category.
• Alarm or warning
The switch output signals diagnostic events in the alarm and warning category.
• Warning
The switch output signals only diagnostic events in the warning category.
Assign limit
Navigation Expert → Output → PFS output 1 to n → Assign limit (0483–1 to n)
Prerequisite • The Switch option is selected in the Operating mode parameter (→ 120).
• The Limit option is selected in the Switch out funct parameter (→ 132).
Description Use this function to select a process variable for the limit function.
Selection • Off
• Volume flow
• Mass flow
• Correct.vol.flow
• Flow velocity
• Conductivity
*
• CorrConductivity
*
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Temperature
*
• Electronic temp.
Factory setting Volume flow
Additional information Description
Behavior of status output when Switch-on value > Switch-off value:
• Process variable > Switch-on value: transistor is conductive
• Process variable < Switch-off value: transistor is non-conductive