Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 133
Additional information Description
If no diagnostic event is pending, the switch output is closed and conductive.
Selection
Alarm
The switch output signals only diagnostic events in the alarm category.
Alarm or warning
The switch output signals diagnostic events in the alarm and warning category.
Warning
The switch output signals only diagnostic events in the warning category.
Assign limit
Navigation  Expert → Output → PFS output 1 to n → Assign limit (0483–1 to n)
Prerequisite The Switch option is selected in the Operating mode parameter (→  120).
The Limit option is selected in the Switch out funct parameter (→  132).
Description Use this function to select a process variable for the limit function.
Selection Off
Volume flow
Mass flow
Correct.vol.flow
Flow velocity
Conductivity
*
CorrConductivity
*
Totalizer 1
Totalizer 2
Totalizer 3
Temperature
*
Electronic temp.
Factory setting Volume flow
Additional information Description
Behavior of status output when Switch-on value > Switch-off value:
Process variable > Switch-on value: transistor is conductive
Process variable < Switch-off value: transistor is non-conductive
* Visibility depends on order options or device settings