Description of device parameters Proline Promag 300 Modbus RS485
94 Endress+Hauser
Corr.cond.offset
Navigation Expert → Sensor → Sensor adjustm. → Variable adjust → Corr.cond.offset (1870)
Prerequisite The On option is selected in the Conduct. measur. parameter (→ 74) parameter.
Description Use this function to enter the zero point shift to trim the corrected conductivity. The
conductivity unit on which the shift is based is μS/cm.
User entry Signed floating-point number
Factory setting 0 S/m
Additional information Description
Corrected value = (factor × value) + offset
Corr.cond.factor
Navigation Expert → Sensor → Sensor adjustm. → Variable adjust → Corr.cond.factor (1871)
Prerequisite The On option is selected in the Conduct. measur. parameter (→ 74) parameter.
Description Use this function to enter a quantity factor for the corrected conductivity. In each case, this
factor refers to the conductivity in μS/cm.
User entry Positive floating-point number
Factory setting 1
Additional information Description
Corrected value = (factor × value) + offset
Flow vel. offset
Navigation Expert → Sensor → Sensor adjustm. → Variable adjust → Flow vel. offset (1879)
Description Use this function to enter the zero point shift for the flow velocity trim. The flow velocity
unit on which the shift is based is m/s.
User entry Signed floating-point number
Factory setting 0 m/s
Additional information Description
Corrected value = (factor × value) + offset