Proline Promag 300 Modbus RS485 Modbus RS485 Register Information
Endress+Hauser 255
"WLAN settings" submenu
Navigation: Expert → Communication → WLAN settings
Parameter Register Data type Access Selection / User entry / User interface →
WLAN (2702) 6178 Integer Read / Write 0 = Disable
1 = Enable
160
WLAN IP address (2711) 8643 to 8649.5 String Read / Write 4 octet: 0 to 255 (in the particular octet) 162
WLAN subnet mask (2709) 8651 to 8657.5 String Read / Write 4 octet: 0 to 255 (in the particular octet) 163
WLAN MAC address (2703) 8602 to 8609.5 String Read Unique 12-digit character string
comprising letters and numbers
163
Security type (2705) 6206 Integer Read / Write 0 = Unsecured
1 = WPA2-PSK
2 = EAP-PEAP MSCHAP2
3 = EAP-TLS
4 = EAP-PEAP NoAuth.
161
WLAN passphrase (2706) 8611 to 8626 String Read / Write 8 to 32-digit character string comprising
numbers, letters and special characters
163
Assign SSID name (2708) 6218 Integer Read / Write 0 = Device tag
1 = User-defined
164
SSID name (2707) 8627 to 8642 String Read / Write Max. 32-digit character string
comprising numbers, letters and special
characters
164
Select antenna (2713) 6102 Integer Read / Write 0 = External antenna
1 = Internal antenna
165
WLAN channel (2704) 6182 Integer Read / Write 1 to 11 164
Apply changes (2712) Integer Read / Write
6.3.7 "Application" submenu
Navigation: Expert → Application
Parameter Register Data type Access Selection / User entry / User interface →
Reset all tot. (2806) 2609 Integer Read / Write 0 = Cancel
1 = Reset + totalize
166