Description of device parameters Proline Promag 300 Modbus RS485
90 Endress+Hauser
Mass flow factor (1846)
→  91
Conduct. offset (1848)
→  91
Conduct. factor (1849)
→  92
Corr. vol offset (1866)
→  92
Corr. vol factor (1867)
→  92
Temp. offset (1868)
→  93
Temp. factor (1869)
→  93
Corr.cond.offset (1870)
→  94
Corr.cond.factor (1871)
→  94
Flow vel. offset (1879)
→  94
Flow vel. factor (1880)
→  95
Vol. flow offset
Navigation  Expert → Sensor → Sensor adjustm. → Variable adjust → Vol. flow offset (1831)
Description Use this function to enter the zero point shift for the volume flow trim. The volume flow
unit on which the shift is based is m³/s.
User entry Signed floating-point number
Factory setting 0 m³/s
Additional information Description
Corrected value = (factor × value) + offset
Vol. flow factor
Navigation  Expert → Sensor → Sensor adjustm. → Variable adjust → Vol. flow factor (1832)
User entry Positive floating-point number
Factory setting 1