Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 103
Assign stat.inp.
Navigation Expert → Input → Status input 1 to n → Assign stat.inp. (1352–1 to n)
Description Use this function to select the function for the status input.
Selection • Off
• Reset totaliz. 1
• Reset totaliz. 2
• Reset totaliz. 3
• Reset all tot.
• Flow override
Factory setting Off
Additional information Custody transfer mode
Only available for Promag H.
NOTE!
Before enabling the measuring device for custody transfer mode, make sure that the Off
option is selected in the Assign stat.inp..
For detailed information on custody transfer mode, see the Special Documentation for
the device → 7
Additional information Selection
• Off
The status input is switched off.
• Reset totaliz. 1…3
The individual totalizers are reset.
• Reset all tot.
All totalizers are reset.
• Flow override
The Flow override (→ 73) is activated.
Note on the Flow override (→ 73):
• The Flow override (→ 73) is enabled as long as the level is at the status input
(continuous signal).
• All other assignments react to a change in level (pulse) at the status input.
Val.stat.inp.
Navigation Expert → Input → Status input 1 to n → Val.stat.inp. (1353–1 to n)
Description Displays the current input signal level.
User interface • High
• Low