Description of device parameters Proline Promag 300 Modbus RS485
42 Endress+Hauser
Additional information Description
For a reset code, contact your Endress+Hauser service organization.
User entry
The reset code can only be entered via:
Web browser
DeviceCare, FieldCare (via interface CDI RJ45)
Fieldbus
Additional parameters in the "Administration" submenu
Device reset
Navigation  Expert → System → Administration → Device reset (0000)
Description Use this function to choose whether to reset the device configuration - either entirely or in
part - to a defined state.
Selection Cancel
To delivery set.
Restart device
Rest.S-DATBackup
Factory setting Cancel
Additional information Selection
Options Description
Cancel No action is executed and the user exits the parameter.
To delivery set. Every parameter for which a customer-specific default setting was ordered is reset
to this customer-specific value. All other parameters are reset to the factory
setting.
Restart device The restart resets every parameter whose data are in the volatile memory (RAM)
to the factory setting (e.g. measured value data). The device configuration remains
unchanged.
Rest.S-DATBackup Restore the data that are saved on the S-DAT. The data record is restored from the
electronics memory to the S-DAT.
Activate SW opt.
Navigation  Expert → System → Administration → Activate SW opt. (0029)
Description Use this function to enter an activation code to enable an additional, ordered software
option.