Description of device parameters Proline Promag 300 Modbus RS485
76 Endress+Hauser
"Low flow cut off" submenu
Navigation  Expert → Sensor → Process param. → Low flow cut off
Low flow cut off
Assign variable (1837)
→  76
On value (1805)
→  76
Off value (1804)
→  77
Pres. shock sup. (1806)
→  77
Assign variable
Navigation  Expert → Sensor → Process param. → Low flow cut off → Assign variable (1837)
Description Use this function to select the process variable for low flow cutoff detection.
Selection Off
Volume flow
Mass flow
Correct.vol.flow
Factory setting Volume flow
On value
Navigation  Expert → Sensor → Process param. → Low flow cut off → On value (1805)
Prerequisite One of the following options is selected in the Assign variable parameter (→  76):
Volume flow
Mass flow
Description Use this function to enter a switch-on value for low flow cut off. Low flow cut off is
activated if the value entered is not equal to 0 →  77.
User entry Positive floating-point number
Factory setting Depends on country and nominal diameter→  213
Additional information Dependency
The unit depends on the process variable selected in the Assign variable parameter
(→  76).