Description of device parameters Proline Promag 300 Modbus RS485
76 Endress+Hauser
"Low flow cut off" submenu
Navigation Expert → Sensor → Process param. → Low flow cut off
‣
Low flow cut off
Assign variable (1837)
→ 76
On value (1805)
→ 76
Off value (1804)
→ 77
Pres. shock sup. (1806)
→ 77
Assign variable
Navigation Expert → Sensor → Process param. → Low flow cut off → Assign variable (1837)
Description Use this function to select the process variable for low flow cutoff detection.
Selection • Off
• Volume flow
• Mass flow
• Correct.vol.flow
Factory setting Volume flow
On value
Navigation Expert → Sensor → Process param. → Low flow cut off → On value (1805)
Prerequisite One of the following options is selected in the Assign variable parameter (→ 76):
• Volume flow
• Mass flow
Description Use this function to enter a switch-on value for low flow cut off. Low flow cut off is
activated if the value entered is not equal to 0 → 77.
User entry Positive floating-point number
Factory setting Depends on country and nominal diameter→ 213
Additional information Dependency
The unit depends on the process variable selected in the Assign variable parameter
(→ 76).