Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 101
Additional information Current input behavior
The current input behaves differently depending on the settings configured in the
following parameters:
Current span (→  100)
Failure mode (→  101)
Configuration examples
Pay attention to the configuration examples for 4 mA value parameter (→  108).
20 mA value
Navigation  Expert → Input → Current input 1 to n → 20 mA value (1607–1 to n)
Description Use this function to enter a value for the 20 mA current.
User entry Signed floating-point number
Factory setting Depends on country and nominal diameter
Additional information Configuration examples
Pay attention to the configuration examples for 4 mA value parameter (→  108).
Failure mode
Navigation  Expert → Input → Current input 1 to n → Failure mode (1601–1 to n)
Description Use this function to select the input behavior when measuring a current outside the
configured Current span parameter (→  100).
Selection Alarm
Last valid value
Defined value
Factory setting Alarm
Additional information Options
Alarm
An error message is set.
Last valid value
The last valid measured value is used.
Defined value
A user-defined measured value is used (Failure value parameter (→  102)).