Description of device parameters Proline Promag 300 Modbus RS485
180 Endress+Hauser
Factory setting All
Additional information Description
The status signals are categorized in accordance with VDI/VDE 2650 and NAMUR
Recommendation NE 107:
• F = Failure
• C = Function Check
• S = Out of Specification
• M = Maintenance Required
"Event list" submenu
The Event list submenu is only displayed if operating via the local display.
If operating via the FieldCare operating tool, the event list can be read out with a
separate FieldCare module.
If operating via the Web browser, the event messages can be found directly in the
Event logbook submenu.
Navigation Expert → Diagnostics → Event logbook → Event list
▸ Event list
Event list
→ 180
Event list
Navigation Expert → Diagnostics → Event logbook → Event list
Description Displays the history of event messages of the category selected in the Filter options
parameter (→ 179).
User interface • For a "Category I" event message
Information event, short message, symbol for event recording and operating time when
error occurred
• For a "Category F, C, S, M" event message (status signal)
Diagnostics code, short message, symbol for event recording and operating time when
error occurred
Additional information Description
A maximum of 20 event messages are displayed in chronological order.
If the Extended HistoROM application package (order option) is enabled in the device, the
event list can contain up to 100 entries .