Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 127
Max. freq. value
Navigation Expert → Output → PFS output 1 to n → Max. freq. value (0454–1 to n)
Prerequisite One of the following options is selected in the Assign curr. parameter (→ 106):
• Volume flow
• Mass flow
• Correct.vol.flow
• Flow velocity
• Conductivity
*
• CorrConductivity
*
• Temperature
*
• Electronic temp.
Description Use this function to enter the end value frequency.
User entry 0.0 to 10 000.0 Hz
Factory setting 10 000.0 Hz
Val. at min.freq
Navigation Expert → Output → PFS output 1 to n → Val. at min.freq (0476–1 to n)
Prerequisite One of the following options is selected in the Assign curr. parameter (→ 106):
• Volume flow
• Mass flow
• Correct.vol.flow
• Flow velocity
• Conductivity
*
• CorrConductivity
*
• Temperature
*
• Electronic temp.
Description Use this function to enter the measured value for the start value frequency.
User entry Signed floating-point number
Factory setting Depends on country and nominal diameter
Additional information Dependency
The entry depends on the process variable selected in the Assign freq. parameter
(→ 126).