Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 143
User entry Signed floating-point number
Factory setting Country-specific:
0 l/h
0 gal(us)/min
Additional information Description
Use this function to enter the limit value for the switch-on value (process variable >
switch-on value = closed, conductive).
When using a hysteresis: Switch-on value > Switch-off value.
Dependency
The unit is dependent on the process variable selected in the Assign limit parameter
(→  140).
Switch-on delay
Navigation  Expert → Output → Relay output 1 to n → Switch-on delay (0814–1 to n)
Prerequisite In the Relay outp.func. parameter (→  139), the Limit option is selected.
Description Use this function to enter a delay time for switching on the switch output.
User entry 0.0 to 100.0 s
Factory setting 0.0 s
Failure mode
Navigation  Expert → Output → Relay output 1 to n → Failure mode (0811–1 to n)
Description Use this function to select the failure mode of the relay output in the event of a device
alarm.
Selection Actual status
Open
Closed
Factory setting Open