Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 139
Assign limit
→  140
Assign diag. beh
→  141
Assign status
→  141
Switch-off value
→  142
Switch-off delay
→  142
Switch-on value
→  142
Switch-on delay
→  143
Failure mode
→  143
Switch status
→  144
Powerless relay
→  144
Terminal no.
Navigation  Expert → Output → Relay output 1 to n → Terminal no. (0812–1 to n)
Description Displays the terminal numbers used by the relay output module.
User interface Not used
24-25 (I/O 2)
22-23 (I/O 3)
Additional information "Not used" option
The relay output module does not use any terminal numbers.
Relay outp.func.
Navigation  Expert → Output → Relay output 1 to n → Relay outp.func. (0804–1 to n)
Description Use this function to select an output function for the relay output.
Selection Closed
Open
Diag. behavior
Limit
Fl. direct.check
Digital Output