Proline Promag 300 Modbus RS485 Modbus RS485 Register Information
Endress+Hauser 247
6.3.4 "Input" submenu
"Current input 1 to n" submenu
Navigation: Expert → Input → Current input 1 to n
Parameter Register Data type Access Selection / User entry / User interface → 
Terminal no. (1611–1 to n) 1: 6548
2: 6549
3: 6550
Integer Read 0 = Not used
2 = 24-25 (I/O 2)
3 = 22-23 (I/O 3)
99
Signal mode (1610–1 to n) 1: 6424
2: 6425
3: 6426
Integer Read / Write 0 = Passive
2 = Active
100
Current span (1605–1 to n) 1: 6147
2: 6148
3: 6149
Integer Read / Write 0 = 4...20 mA
1 = 4...20 mA US
2 = 4...20 mA NAMUR
(+)
3 = 0...20 mA
100
0/4 mA value (1606–1 to n) 1: 6111 to 6112
2: 6113 to 6114
3: 6115 to 6116
Float Read / Write Signed floating-point number 100
20 mA value (1607–1 to n) 1: 6119 to 6120
2: 6121 to 6122
3: 6123 to 6124
Float Read / Write Signed floating-point number 101
Failure mode (1601–1 to n) 1: 6159
2: 6160
3: 6161
Integer Read / Write 1 = Last valid value
2 = Alarm
6 = Defined value
101
Failure value (1602–1 to n) 1: 6163 to 6164
2: 6165 to 6166
3: 6167 to 6168
Float Read / Write Signed floating-point number 102
"Status input 1 to n" submenu
Navigation: Expert → Input → Status input 1 to n
Parameter Register Data type Access Selection / User entry / User interface → 
Terminal no. (1358–1 to n) 1: 6554
2: 6555
3: 6556
Integer Read 0 = Not used
2 = 24-25 (I/O 2)
3 = 22-23 (I/O 3)
102
Assign stat.inp. (1352–1 to n) 1: 2506
2: 4687
3: 4688
Integer Read / Write 0 = Off
1 = Flow override
2 = Reset all tot.
3 = Reset totaliz. 1
4 = Reset totaliz. 2
5 = Reset totaliz. 3
103
Val.stat.inp. (1353–1 to n) 1: 2746
2: 4699
3: 4700
Integer Read 9 = Low
10 = High
103
Active level (1351–1 to n) 1: 2530
2: 4690
3: 4691
Integer Read / Write 9 = Low
10 = High
104
Response time (1354–1 to n) 1: 3404 to 3405
2: 5753 to 5754
3: 5755 to 5756
Float Read / Write 5 to 200 ms 104