Description of device parameters Proline Promag 300 Modbus RS485
132 Endress+Hauser
Switch out funct
Navigation  Expert → Output → PFS output 1 to n → Switch out funct (0481–1 to n)
Prerequisite The Switch option is selected in the Operating mode parameter (→  120).
Description Use this function to select a function for the switch output.
Selection Off
On
Diag. behavior
Limit
Fl. direct.check
Status
Factory setting Off
Additional information Selection
Off
The switch output is permanently switched off (open, non-conductive).
On
The switch output is permanently switched on (closed, conductive).
Diag. behavior
Indicates if the diagnostic event is present or not. Is used to output diagnostic
information and to react to it appropriately at the system level.
Limit
Indicates if a specified limit value has been reached for the process variable. Is used to
output diagnostic information relating to the process and to react to it appropriately at
the system level.
Fl. direct.check
Indicates the flow direction (forward or reverse flow).
Status
Indicates the device status depending on whether empty pipe detection or low flow cut
off is selected.
Assign diag. beh
Navigation  Expert → Output → PFS output 1 to n → Assign diag. beh (0482–1 to n)
Prerequisite In the Operating mode parameter (→  120), the Switch option is selected.
In the Switch out funct parameter (→  132), the Diag. behavior option is selected.
Description Use this function to select the diagnostic event category that is displayed for the switch
output.
Selection Alarm
Alarm or warning
Warning
Factory setting Alarm