Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 205
Value curr.inp 1 to n
Navigation Expert → Diagnostics → Simulation → Value curr.inp 1 to n (1609–1 to n)
Prerequisite In the Curr.inp 1 to n sim. parameter, the On option is selected.
Description Use this function to enter the current value for the simulation. In this way, users can verify
the correct configuration of the current input and the correct function of upstream feed-in
units.
User entry 0 to 22.5 mA
Curr.out. 1 to n sim.
Navigation Expert → Diagnostics → Simulation → Curr.out. 1 to n sim. (0354–1 to n)
Description Use this function to switch simulation of the current output on and off. The display
alternates between the measured value and a diagnostic message of the "Function check"
category (C) while simulation is in progress.
Selection • Off
• On
Factory setting Off
Additional information Description
The desired simulation value is defined in the Value curr.out 1 to n parameter.
Selection
• Off
Current simulation is switched off. The device is in normal measuring mode or another
process variable is being simulated.
• On
Current simulation is active.
Value curr.out 1 to n
Navigation Expert → Diagnostics → Simulation → Value curr.out 1 to n (0355–1 to n)
Prerequisite In the Curr.out. 1 to n sim. parameter, the On option is selected.
Description Use this function to enter a current value for the simulation. In this way, users can verify
the correct adjustment of the current output and the correct function of downstream
switching units.
User entry 3.59 to 22.5 mA