Description of device parameters Proline Promag 300 Modbus RS485
106 Endress+Hauser
Selection Passive
Active
Factory setting Active
Assign curr. 1 to n
Navigation  Expert → Output → Curr.output 1 to n → Assign curr. 1 to n (0359–1 to n)
Description Use this function to select a process variable for the current output.
Selection Off
Volume flow
Mass flow
Correct.vol.flow
Flow velocity
Conductivity
*
CorrConductivity
*
Temperature
*
Electronic temp.
Factory setting Volume flow
Current span
Navigation  Expert → Output → Curr.output 1 to n → Current span (0353–1 to n)
Description Use this function to select the current range for the process value output and the upper
and lower level for signal on alarm.
Selection 4...20 mA NAMUR
4...20 mA US
4...20 mA
0...20 mA
Fixed current
Factory setting Country-specific:
4...20 mA NAMUR
4...20 mA US
* Visibility depends on order options or device settings