EasyManua.ls Logo

Endress+Hauser Proline Promag 300 - Clear Logging; Data Logging

Endress+Hauser Proline Promag 300
272 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of device parameters Proline Promag 300 Modbus RS485
194 Endress+Hauser
Additional information Description
This defines the interval between the individual data points in the data log, and thus the
maximum loggable process time T
log
:
If 1 logging channel is used: T
log
= 1000 × t
log
If 2 logging channels are used: T
log
= 500 × t
log
If 3 logging channels are used: T
log
= 333 × t
log
If 4 logging channels are used: T
log
= 250 × t
log
Once this time elapses, the oldest data points in the data log are cyclically overwritten such
that a time of T
log
always remains in the memory (ring memory principle).
The log contents are cleared if the length of the logging interval is changed.
Example
If 1 logging channel is used:
T
log
= 1000 × 1 s = 1 000 s ≈15 min
T
log
= 1000 × 10 s = 10 000 s ≈ 3 h
T
log
= 1000 × 80 s = 80 000 s ≈ 1 d
T
log
= 1000 × 3 600 s = 3 600 000 s ≈ 41 d
Clear logging
Navigation  Expert → Diagnostics → Data logging → Clear logging (0855)
Prerequisite The Extended HistoROM application package is available.
The software options currently enabled are displayed in the SW option overv.
parameter (→  43).
Description Use this function to clear the entire logging data.
Selection Cancel
Clear data
Factory setting Cancel
Additional information Selection
Cancel
The data is not cleared. All the data is retained.
Clear data
The logging data is cleared. The logging process starts from the beginning.
Data logging
Navigation  Expert → Diagnostics → Data logging → Data logging (0860)
Description Use this function to select the data logging method.
Selection Overwriting
Not overwriting

Table of Contents