Description of device parameters Proline Promag 300 Modbus RS485
48 Endress+Hauser
"Totalizer" submenu
Navigation Expert → Sensor → Measured val. → Totalizer
‣
Totalizer
Totalizer val. 1 to n (0911–1 to n)
→ 48
Tot. overflow 1 to n (0910–1 to n)
→ 48
Totalizer val. 1 to n
Navigation Expert → Sensor → Measured val. → Totalizer → Totalizer val. 1 to n (0911–1 to n)
Prerequisite A process variable is selected in the Assign variable parameter (→ 167) of the
Totalizer 1 to n submenu.
Description Displays the current totalizer reading.
User interface Signed floating-point number
Additional information Description
As it is only possible to display a maximum of 7 digits in the operating tool, the current
counter value is the sum of the totalizer value and the overflow value from the Tot.
overflow 1 to n parameter if the display range is exceeded.
In the event of an error, the totalizer adopts the mode defined in the Failure mode
parameter (→ 170).
User interface
The value of the process variable totalized since measuring began can be positive or
negative. This depends on the settings in the Operation mode parameter (→ 169).
The unit of the selected process variable is specified for the totalizer in the Unit
totalizer parameter (→ 168).
Example
Calculation of the current totalizer reading when the value exceeds the 7-digit display
range of the operating tool:
• Value in the Totalizer val. 1 parameter: 1 968 457 m
3
• Value in the Tot. overflow 1 parameter: 1 ⋅ 10
7
(1 overflow) = 10 000 000 [m
3
]
• Current totalizer reading: 11 968 457 m
3
Tot. overflow 1 to n
Navigation Expert → Sensor → Measured val. → Totalizer → Tot. overflow 1 to n (0910–1 to n)
Prerequisite A process variable is selected in the Assign variable parameter (→ 167) of the
Totalizer 1 to n submenu.