"Diagn. behavior" submenu
Each item of diagnostic information is assigned a specific diagnostic behavior at the
factory. The user can change this assignment for specific diagnostic information in the
Diagn. behavior submenu (→ 32).
The following options are available in the Assign behavior of diagnostic no. xxx
parameters:
Options Description
Alarm The device stops measurement. The measured value output via Modbus RS485 and the
totalizers assume the defined alarm condition. A diagnostic message is generated.
The background lighting changes to red.
Warning The device continues to measure. The measured value output via Modbus RS485 and the
totalizers are not affected. A diagnostic message is generated.
Logbook only The device continues to measure. The diagnostic message is displayed only in the Event
logbook submenu (→ 179) (Event list submenu (→ 180)) and is not displayed in
alternation with the operational display.
Off The diagnostic event is ignored, and no diagnostic message is generated or entered.
For a list of all the diagnostic events, see the Operating Instructions for the device
→ 7
Navigation Expert → System → Diagn. handling → Diagn. behavior
‣
Diagn. behavior
Diagnostic no. 043 (0650)
→ 33
Diagnostic no. 302 (0739)
→ 33
Diagnostic no. 376 (0645)
→ 34
Diagnostic no. 377 (0777)
→ 34
Diagnostic no. 441 (0657)
→ 34
Diagnostic no. 442 (0658)
→ 35
Diagnostic no. 443 (0659)
→ 35
Diagnostic no. 444 (0740)
→ 35
Diagnostic no. 543 (0643)
→ 36
Diagnostic no. 531 (0741)
→ 36
Diagnostic no. 832 (0681)
→ 37
Diagnostic no. 833 (0682)
→ 37
Diagnostic no. 834 (0700)
→ 37