Modbus RS485 Register Information Proline Promag 300 Modbus RS485
248 Endress+Hauser
6.3.5 "Output" submenu
"Curr.output 1 to n" submenu
Navigation: Expert → Output → Curr.output 1 to n
Parameter Register Data type Access Selection / User entry / User interface → 
Terminal no. (0379–1 to n) 1: 6545
2: 6546
3: 6547
Integer Read 0 = Not used
2 = 24-25 (I/O 2)
3 = 22-23 (I/O 3)
105
Signal mode (0377–1 to n) 1: 6421
2: 6422
3: 6423
Integer Read / Write 0 = Passive
2 = Active
105
Assign curr. 1 to n (0359–1 to n) 1: 5927
2: 5928
3: 5929
Integer Read / Write 0 = Off
1 = Volume flow
2 = Mass flow
3 = Correct.vol.flow
4 = Conductivity
*
7 = Temperature
*
9 = CorrConductivity
*
37 = Flow velocity
39 = Electronic temp.
106
Current span (0353–1 to n) 1: 5923
2: 5924
3: 5925
Integer Read / Write 0 = 4...20 mA
1 = 4...20 mA US
2 = 4...20 mA NAMUR
3 = 0...20 mA
4 = Fixed current
106
Fixed current (0365–1 to n) 1: 5987 to 5988
2: 5989 to 5990
3: 5991 to 5992
Float Read / Write 0 to 22.5 mA 107
0/4 mA value (0367–1 to n) 1: 6195 to 6196
2: 6197 to 6198
3: 6199 to 6200
Float Read / Write Signed floating-point number 108
20 mA value (0372–1 to n) 1: 5915 to 5916
2: 5917 to 5918
3: 5919 to 5920
Float Read / Write Signed floating-point number 109
Measuring mode (0351–1 to n) 1: 5899
2: 5900
3: 5901
Integer Read / Write 0 = Forward flow
2 = Rev. flow comp.
13 = Forward/Reverse
110
Damping out. 1 to n (0363–1 to n) 1: 5903 to 5904
2: 5905 to 5906
3: 5907 to 5908
Float Read / Write 0.0 to 999.9 s 114
Response time (0378–1 to n) 1: 5867 to 5868
2: 5869 to 5870
3: 5871 to 5872
Float Read Positive floating-point number 115
Failure mode (0364–1 to n) 1: 5911
2: 5912
3: 5913
Integer Read / Write 0 = Min.
1 = Max.
4 = Actual value
5 = Last valid value
6 = Defined value
116
Failure current (0352–1 to n) 1: 5979 to 5980
2: 5981 to 5982
3: 5983 to 5984
Float Read / Write 0 to 22.5 mA 117
Output curr. 1 to n (0361–1 to n) 1: 5931 to 5932
2: 5933 to 5934
3: 5935 to 5936
Float Read 3.59 to 22.5 mA 117
Measur. curr. 1 to n (0366–1 to n) 1: 5779 to 5780
2: 5781 to 5782
3: 5783 to 5784
Float Read 0 to 30 mA 118
* Visibility depends on order options or device settings