Proline Promag 300 Modbus RS485 Description of device parameters
Endress+Hauser 35
Diagnostic no. 442 (Freq. output 1 to n)
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 442 (0658)
Prerequisite The measuring device has a pulse/frequency/switch output.
Description Use this function to change the diagnostic behavior of the diagnostic message 442 Freq.
output 1 to n.
Selection • Off
• Alarm
• Warning
• Logbook only
Factory setting Warning
Additional information For a detailed description of the options available, see → 32
Diagnostic no. 443 (Pulse output 1 to n)
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 443 (0659)
Prerequisite The measuring device has a pulse/frequency/switch output.
Description Use this function to change the diagnostic behavior of the diagnostic message 443 Pulse
output 1 to n.
Selection • Off
• Alarm
• Warning
• Logbook only
Factory setting Warning
Additional information For a detailed description of the options available, see → 32
Diagnostic no. 444 (Current input 1 to n)
Navigation Expert → System → Diagn. handling → Diagn. behavior → Diagnostic no. 444 (0740)
Prerequisite The device has one current input.
Description Use this function to change the diagnostic behavior of the diagnostic message
444 Current input 1 to n.