Description of device parameters Proline Promag 300 Modbus RS485
110 Endress+Hauser
smaller than the value assigned for the 0/4 mA current in the 0/4 mA value parameter
(→  108).
Dependency
The unit depends on the process variable selected in the Assign curr. parameter
(→  106).
Example
Value assigned to 0/4 mA = –250 m
3
/h
Value assigned to 20 mA = +750 m
3
/h
Calculated current value = 8 mA (at zero flow)
If the Forward/Reverse option is selected in the Measuring mode parameter
(→  110), different signs cannot be entered for the values of the 0/4 mA value
parameter (→  108) and 20 mA value parameter (→  109). The diagnostic message
S441 Curr.output 1 to n is displayed.
Configuration examples
Observe the configuration examples for the 0/4 mA value parameter (→  108).
Measuring mode
Navigation  Expert → Output → Curr.output 1 to n → Measuring mode (0351–1 to n)
Prerequisite One of the following options is selected in the Assign curr. parameter (→  106):
Volume flow
Mass flow
Correct.vol.flow
Flow velocity
Conductivity
*
CorrConductivity
*
Temperature
*
Electronic temp.
One of the following options is selected in the Current span parameter (→  106):
4...20 mA NAMUR
4...20 mA US
4...20 mA
0...20 mA
Description Use this function to select the measuring mode for the current output.
Selection Forward flow
Forward/Reverse
Rev. flow comp.
Factory setting Forward flow
* Visibility depends on order options or device settings