Description of device parameters Proline Promag 300 Modbus RS485
110 Endress+Hauser
smaller than the value assigned for the 0/4 mA current in the 0/4 mA value parameter
(→ 108).
Dependency
The unit depends on the process variable selected in the Assign curr. parameter
(→ 106).
Example
• Value assigned to 0/4 mA = –250 m
3
/h
• Value assigned to 20 mA = +750 m
3
/h
• Calculated current value = 8 mA (at zero flow)
If the Forward/Reverse option is selected in the Measuring mode parameter
(→ 110), different signs cannot be entered for the values of the 0/4 mA value
parameter (→ 108) and 20 mA value parameter (→ 109). The diagnostic message
S441 Curr.output 1 to n is displayed.
Configuration examples
Observe the configuration examples for the 0/4 mA value parameter (→ 108).
Measuring mode
Navigation Expert → Output → Curr.output 1 to n → Measuring mode (0351–1 to n)
Prerequisite One of the following options is selected in the Assign curr. parameter (→ 106):
• Volume flow
• Mass flow
• Correct.vol.flow
• Flow velocity
• Conductivity
*
• CorrConductivity
*
• Temperature
*
• Electronic temp.
One of the following options is selected in the Current span parameter (→ 106):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Description Use this function to select the measuring mode for the current output.
Selection • Forward flow
• Forward/Reverse
• Rev. flow comp.
Factory setting Forward flow
* Visibility depends on order options or device settings